ENMET Corporation PO Box 979 Ann Arbor, MI 48106-0979 Manual part number 80003-096 MCN-416, 04/03/09 EX-5100 COMBUSTIB
ENMET Corporation EX-5100 COMBUSTIBLE 8 5.0 Maintenance of the EX-5100 CAUTION: Do not open the EX-5100 S/T in a classified area. CAUTION: Do Not
EX-5100 COMBUSTIBLE ENMET Corporation 9 5.2 Calibration of the EX-5100 Calibration is the process of setting the instrument up to read accurately
ENMET Corporation EX-5100 COMBUSTIBLE 10 Calibration: Calibration of Standard Gases: Calibration of the EX-5100 should be preformed using the tar
EX-5100 COMBUSTIBLE ENMET Corporation 11 5.2.1 Zero Adjust A ZERO function should be performed only when the EX-5100 sensor/transmitter is expose
ENMET Corporation EX-5100 COMBUSTIBLE 12 Normal Display Mode SelectMenu0LEL MENU HOLD the magnet over the MENU switch for 2 – 4 seconds
EX-5100 COMBUSTIBLE ENMET Corporation 13 5.3 Heater Voltage Settings Heater Voltages are necessary for Catalytic sensors. They are preset at the
ENMET Corporation EX-5100 COMBUSTIBLE 14 6.0 Replacement Part Numbers ENMET replacement part numbers: Description Part Number Sensor, Catalytic
PO Box 979 680 Fairfield Court Ann Arbor, Michigan 48106-0979 734.761.1270 Fax 734.761.3220 Returning an Instrument for Repair ENMET instrume
Repair Return Form Mailing Address: ENMET Corporation PO Box 979 Ann Arbor, Michigan 48106 Phone Number: 734.761.1270 FAX Number: 734.
Table of Contents 1.0 INTRODUCTION ...
EX-5100 COMBUSTIBLE ENMET Corporation 1 1.0 Introduction The ENMET EX-5100 sensor/transmitters (S/T) is, 3-wire, 24VDC 4-20 ma S/T for the detec
ENMET Corporation EX-5100 COMBUSTIBLE 2 2.0 Features of the EX-5100 See Figure 1 for location of features: Feature Description Display LCD: Indi
EX-5100 COMBUSTIBLE ENMET Corporation 3 3.0 Installation of the EX-5100 CAUTION: Area must be declassified during installation. The ENMET EX-5100
ENMET Corporation EX-5100 COMBUSTIBLE 4 3.2 Wiring the EX-5100 to a Control Unit CAUTION: Area must be declassified during installation. Run cond
EX-5100 COMBUSTIBLE ENMET Corporation 5 EX-5100 Interior Expanded View EX-5100 Interior Assembled View Figure 3: Terminal Positions EX-510
ENMET Corporation EX-5100 COMBUSTIBLE 6 4.0 Operation of the EX-5100 It is best to have the EX-5100 transmitters powered up and operational for 2
EX-5100 COMBUSTIBLE ENMET Corporation 7 4.2 Normal Display Mode When the EX-5100 is installed as described in section 3, and in clean air, the PO